Water Reduction

Is your sand filter backflushing daily or more frequently? Only backflush when the pressure differential indicates a dirty sand filter.See your sand filter owner’s manual for recommendations.

If your cooling tower or boiler conductivity is not operating at its conductivity/TDS setpoint, find out why. The most common reasons for low conductivity are:

– Leaking solenoid bleed valves
– Overflowing cooling towers, check the float or level control!
– Manual boiler blowdown, poor control over conductivity
– Leaks within the plant

How often are you blowing down the boiler? Ask your service representative for a recommendation. Systems with high purity or soft water do not require as much blowdown as you may think.

Is your boiler TDS/Conductivity maximized? A.S.M.E. guidelines allow for relatively high conductivities providing you have good quality feedwater. If your feedwater quality is not up to par, we can help get it there! Ask your service representative for more information.

Are you losing condensate from your steam boiler? Repairing condensate leaks not only saves water, but the heat content is very valuable and will reduce your boiler fuel usage.

Does your closed chilled or hot water loop make up water? Finding the leak saves water and reduces corrosion and scale in the loop. We can provide a tracer dye to help locate leaks. Pump seals and pressure relief valves are common items that leak.

Are you using once-through cooling for equipment? Either convert it to a closed cooling loop or take that water and re-direct it from the drain to another water user (cooling tower).

UET

GREEN Machine Benefits:
Elimination of acid based scale control additives
Maximum water conservation and cost reduction
Safety enhancement
Reduce or eliminate inhibitor & biocide additives
Hands-free operation
Total Water Management contracting for net + $ flow
Green application for LEED points and tax credits


Cycles of Concentration are simply the number of times the cooling tower water is concentrated when compared to make up water. For example, if your make up water TDS is 500 ppm and your cooling tower TDS is 1500, you are running 3 cycles of concentration.

Cooling towers that use Denver Water make up can typically save 40% of bleed rates with a relatively simple change in their chemical program. Savings of 60% or more are attainable with upgraded feed and control equipment.

Steam boiler water use can also be reduced with the appropriate chemical program and feedwater quality. Is your boiler blowing down too much? Not only will you save water and chemicals by reducing blowdown, but fuel savings can easily amount to $40,000++ per year for a 500 HP boiler.

What can your plant save? Call us now and we’ll provide a quick and free analysis of your water use and let you know what savings options are available!

To date, we have helped customers save 197 million gallons of water per year! We have the experience, products, and equipment necessary to help you reduce water and do your part for Colorado’s drought conditions

Useful Links

Denver Water – drought surcharge information, water quality, water use tips, watering calendar, etc.
NOTICE: Get $500 credit towards the purchase of a new cooling tower conductivity controller or $50 towards the purchase of a water meter (Denver metro area customers).

Colorado Springs Utilities Water Saver – Reservoir water pictures, water saving tips, etc.

USDA Snowpack information page

Colorado Division of Water Resources – real time stream flows, etc.

US Drought Monitor map